Sample dataUSS Longhorns (DDG 2004), 7 open, 2 waiting on your answer
OI-07
Needs your input
Cable tray clashes with a vent duct
- Space
- 2-170-2-Q
- Alteration
- ALT-101
- Logged
- Today, 09:58
- Answer by
- Oct 29
What we found
The new cable tray runs into an existing vent duct near frame 172. The drawing shows clear space there.
What we propose
Route the tray under the duct with two added hangers. Cable lengths do not change, and the schedule holds if we hear back by October 29.
Weaver Maritime Technologies planner, 10:20
Photos and a sketch of the reroute are in the approved records system under OI-07.